1. Product Details

  2. Variations

  3. Variations

  4. Literature

Detailed Description

The ETF 012 senses the ambient temperature and relative air humidity in an enclosure.

  • Efficient temperature & humidity control
  • Wide voltage range
  • Operating temperature down to -40°C
  • High switching capacity
  • DIN rail mountable

Technical Data
Switching difference (temperature): 2 K (±1 K tolerance) at +25°C (+77°F), 50% RH
Switching difference (humidity): 4% RH (±1% tolerance) at +25°C (+77°F), 50% RH
Reaction time: approx. 5 seconds
Contact type: change-over contact (relay)
Service life: > VDE: NO/NC > 15,000 cycles
UL: NO/NC > 30,000 cycles
Max. switching capacity (relay output): 10 A resistive / 1.6 A inductive @ AC 240 V
0.6 A @ DC 60 V¹
Max. inrush current: AC 30 A for 10 sec.
Connection: 5-pole terminal, clamping torque 0.5 Nm max.:
solid/stranded² wire – AWG 14 max. (2.5 mm²)
Housing: plastic, UL 94V-0, light grey
Mounting: clip for 35 mm DIN rail, EN 60715
Mounting position: vertical
Dimensions: 3.0 x 2.4 x 1.7” (77 x 60 x 43 mm)
Weight: approx. 3.5 oz. (100 g)
Operating/Storage temperature: -40 to +140°F (-40 to +60°C)
Operating/Storage humidity: max. 90% RH (non-condensing)
Protection type: IP20
Approvals: UL File No. E164102 / VDE / EAC
¹ not UL confirmed
² When connecting with stranded wires, wire end ferrules must be used.

Variations

  1. ETF 012: 01230.0-00

    Operating voltage:
    AC 100-240 V, 50/60 Hz
    (min. AC 90 V, max. AC 265 V)
    Setting range – temperature:
    0 to +60°C
    Setting range – humidity:
    50 to 90% RH

  2. ETF 012: 01230.9-00

    Operating voltage:
    AC 100-240 V, 50/60 Hz
    (min. AC 90 V, max. AC 265 V)
    Setting range – temperature:
    +32 to +140°F
    Setting range – humidity:
    50 to 90% RH

  3. ETF 012: 01230.1-00

    Operating voltage:
    DC 24-48 V
    (min. DC 20 V, max. DC 60 V)
    Setting range – temperature:
    0 to +60°C
    Setting range – humidity:
    50 to 90% RH