- For use in hazardous areas
- High switching capacity
- Compact Design
- “Pre-set” temperature
- Ready-to-use with strain relief
- Temperature class T6
Technical Data
Temperature class: T6
Ex Protection type Ex II 2 GD
Gases: Ex db IIC T6 Gb
Dusts Ex tb IIIC T85 °C Db IP66
Ambient temperature: -76 to +140 °F (-60 to +60 °C)
Sensor element: thermostatic bimetal
Service life: > 100,000 cycles
Max. switching capacity: 10 A¹ resistive @ AC 250 V,
1 A resistive @ DC 24 V
Min. switching capacity: DC 1.5 V 5 mA
Max. inrush current: AC 16 A for 12 sec.
Connection: silicone cable (halogen-free) 3 x AWG 18 (1.0 mm²)
Connection PE: AWG 18 to 14 (1.0 to 2.5 mm²)
Mounting: clip for 35 mm DIN rail, EN 60715 screw mounting M5, optional sideways mounting
Housing: aluminum, silver anodized
Dimensions: 3.7 x 1.8 x 1.9” (95 x 45 x 30 mm)
Weight: approx. 0.66 lbs (0.3 kg)
Mounting position: variable
Storage temperature: -76 to +185 °F (-60 to +85 °C)
Operating / Storage humidity: max. 90 % RH (non-condensing)
Protection type / Protection class: IP66 / I (grounded)
Approvals: EPS 16 ATEX 1 118 X, IECEx EPS 16.0054X, EAC
¹ currents above 4 A affect the switching difference