1. Product Details

  2. Variations

  3. Variations

  4. Literature

Detailed Description

These heaters are used in enclosures where damage from condensation must be prevented, or where the temperature must be maintained above a minimum value.

  • Compact size
  • Wide voltage range
  • Heating power adjusts to ambient temperature
  • Cage clamp connectors for quick & easy wiring
  • DIN rail mountable

Technical Data
Operating voltage¹: AC/DC 120-240 V (min. 110 V, max. 265 V)
Heating element: PTC resistor, temperature limiting
Heater body: extruded aluminum profile, anodized
Connection: 3 cage clamps for solid wire AWG 20-14 (0.5-2.5 mm²), and
stranded wire (with wire end ferrule) – AWG 20-16 (0.5-1.5 mm²)
Connection casing: plastic, UL 94V-0, black
Mounting: clip for 35 mm DIN rail, EN 60715
Mounting position: vertical airflow (air outlet up, connection on bottom)
Operating / Storage temperature:-49 to +158 °F (-45 to +70 °C)
Operating / Storage humidity: max. 90 %RH (non-condensing)
Protection class / type: I (grounded) / IP44
Approvals: UL File No. E150057 / VDE / EAC
¹ Operating high voltage heaters below AC/DC 140 V reduces heating performance by approx. 10%

Variations

  1. HG 140: 14000.0-00

    Heating capacity¹: 15 W
    Operating voltage²:
    AC/DC 120-240 V
    Max. current (inrush): 1.5 A
    Rec. pre-fuse T (time-delay): 2.0 A

    Length (L): 2.56” (65 mm)
    Weight (approx.): 7.6 oz. (215 g)

    ¹ at 68°F (20°C) ambient temperature
    ² operating high voltage heaters below AC/DC 140V reduces heating performance by approx. 10% (min. 110V, max 265V).

  2. HG 140: 14001.0-00

    Heating capacity¹: 30 W
    Operating voltage²:
    AC/DC 120-240 V
    Max. current (inrush): 3.0 A
    Rec. pre-fuse T (time-delay): 4.0A

    Length (L): 2.56” (65 mm)
    Weight (approx.): 7.6 oz. (215 g)

    ¹ at 68°F (20°C) ambient temperature
    ² operating high voltage heaters below AC/DC 140V reduces heating performance by approx. 10% (min. 110V, max 265V).

  3. HG 140: 14003.0-00

    Heating capacity¹: 45 W
    Operating voltage²:
    AC/DC 120-240 V
    Max. current (inrush): 3.5 A
    Rec. pre-fuse T (time-delay): 4.0A

    Length (L): 2.56” (65 mm)
    Weight (approx.): 7.6 oz. (215 g)

    ¹ at 68°F (20°C) ambient temperature
    ² operating high voltage heaters below AC/DC 140V reduces heating performance by approx. 10% (min. 110V, max 265V).

  4. HG 140: 14005.0-00

    Heating capacity¹: 60 W
    Operating voltage²:
    AC/DC 120-240 V
    Max. current (inrush): 2.5 A
    Rec. pre-fuse T (time-delay): 4.0 A

    Length (L): 5.5” (140 mm)
    Weight (approx.): 14.1 oz. (400 g)

    ¹ at 68°F (20°C) ambient temperature
    ² operating high voltage heaters below AC/DC 140V reduces heating performance by approx. 10% (min. 110V, max 265V).

  5. HG 140: 14006.0-00

    Heating capacity¹: 75 W
    Operating voltage²:
    AC/DC 120-240 V
    Max. current (inrush): 4.0 A
    Rec. pre-fuse T (time-delay): 6.3 A

    Length (L): 5.5” (140 mm)
    Weight (approx.): 14.3 oz. (405 g)

    ¹ at 68°F (20°C) ambient temperature
    ² operating high voltage heaters below AC/DC 140V reduces heating performance by approx. 10% (min. 110V, max 265V).

  6. HG 140: 14007.0-00

    Heating capacity¹: 100 W
    Operating voltage²:
    AC/DC 120-240 V
    Max. current (inrush): 4.5 A
    Rec. pre-fuse T (time-delay): 8.0 A

    Length (L): 5.5” (140 mm)
    Weight (approx.): 14.3 oz. (405 g)

    ¹ at 68°F (20°C) ambient temperature
    ² operating high voltage heaters below AC/DC 140V reduces heating performance by approx. 10% (min. 110V, max 265V).

  7. HG 140: 14008.0-00

    Heating capacity¹: 150 W
    Operating voltage²:
    AC/DC 120-240 V
    Max. current (inrush): 9.0 A
    Rec. pre-fuse T (time-delay): 10.0 A

    Length (L): 8.66” (220 mm)
    Weight (approx.): 14.3 oz. (405 g)

    ¹ at 68°F (20°C) ambient temperature
    ² operating high voltage heaters below AC/DC 140V reduces heating performance by approx. 10% (min. 110V, max 265V).