1. Product Details

  2. Variations

  3. Variations

  4. Literature

Detailed Description

The EFR 012 electronic hygrostat senses the relative humidity in an enclosure and turns on a heater at the set point, helping prevent the formation of condensation in the enclosure.

  • Adjustable & pre-set relative humidity setpoints
  • Compact design
  • High switching capacity
  • Optical function display (LED)
  • DIN rail mountable

Technical Data
Switching difference: 5% RH (± 1% tolerance) – at 77°F (25°C) and 50% RH
Reaction time: approx. 5 seconds
Contact type: SPDT / change-over contact (relay)
Service life: >50,000 cycles
Max. switching capacity (relay output): 8 A resistive / 1.6 A inductive @ AC 120 V
8 A resistive / 1.6 A inductive @ AC 240 V
100 W @ DC 24 V
Max. inrush current: AC 16 A for 10 sec.
Connection: 5-pole terminal, clamping torque 0.5 Nm max.:
solid/stranded¹ wire – AWG 14 max. (2.5 mm²)
Housing: plastic, UL 94V-0, light grey
Mounting: clip for 35 mm DIN rail, EN 60715
Mounting position: vertical
Dimensions: 2.54 x 1.65 x 1.5” (64.5 x 42 x 38 mm)
Weight: approx. 2.3 oz. (65 g)
Operating/Storage temperature: +32 to +140°F / -4 to +158°F
Operating/Storage humidity: max. 90% RH (non-condensing)
Protection type: IP20
¹ When connecting with stranded wires, wire end ferrules must be used.

Variations

  1. EFR 012: 01245.0-00

    Operating voltage: AC 230 V, 50/60 Hz
    Setting range: 40 to 90% RH
    Approvals: UL File No. E164102 / VDE / EAC

  2. EFR 012: 01245.9-00

    Operating voltage: AC 120 V, 50/60 Hz
    Setting range: 40 to 90% RH
    Approvals: UL File No. E164102 / – / EAC

  3. EFR 012: 01246.0-00

    Operating voltage: AC 230 V, 50/60 Hz
    Setting range: 65% RH pre-set
    Approvals: UL File No. E164102 / VDE / EAC

  4. EFR 012: 01246.0-01

    Operating voltage: AC 230 V, 50/60 Hz
    Setting range: 50% RH pre-set
    Approvals: UL File No. E164102 / VDE / EAC

  5. EFR 012: 01246.9-00

    Operating voltage: AC 120 V, 50/60 Hz
    Setting range: 65% RH pre-set
    Approvals: UL File No. E164102 / – / EAC