1. Product Details

  2. Variations

  3. Variations

  4. Literature

Detailed Description

The electronic hygrostat is used for controlling heating and cooling equipment, filter fans or signal devices through the Relay DCM 010 or a similar device.

  • Large setting range
  • Compact design
  • Small hysteresis
  • Optical function display
  • Signal application

Technical Data
Switching difference: 5% RH (± 1% tolerance) – at 77°F (25°C) and 50% RH
Reaction time: approx. 5 seconds
Contact type: SPDT / change-over contact (relay)
Service life: > 100,000 cycles (at 10 mW)
Max. switching capacity (relay output): 80.5 A at DC 48 V
Min. switching load: DDC 10 mW (at 0.1 V, 100 mA or 1 mA, 10 V)
Optical indicator: LED
Connection: 5-pole terminal, clamping torque 0.5 Nm max.:
solid/stranded¹ wire – AWG 14 max. (2.5 mm²)
Housing: plastic, UL 94V-0, light grey
Mounting: clip for 35 mm DIN rail, EN 60715
Mounting position: vertical
Dimensions: 2.54 x 1.65 x 1.5” (64.5 x 42 x 38 mm)
Weight: approx. 2.3 oz. (65 g)
Operating/Storage temperature: +32 to +140°F / -4 to +158°F
Operating/Storage humidity: max. 95% RH (non-condensing)
Protection type: IP20
¹ When connecting with stranded wires, wire end ferrules must be used.

Variations

  1. EFL 012: 01245.2-00

    Operating voltage: DC 12-48 V (min. DC 10 V, max. DC 60 V)
    Setting range: 40 to 90% RH
    Approvals: UL File No. E164102 / EAC