1. Product Details

  2. Variations

  3. Variations

  4. Literature

Detailed Description

The electronic thermostat with integrated switch module is used to control DC powered devices with high capacities in control and switch cabinets.

  • High DC switching capacity
  • Adjustable temperature
  • Small hysteresis
  • Optical operating display (LED)
  • Integrated switch module
  • Precise measurement via an external sensor

Technical Data
Switch temperature difference: 3 K (±1 K tolerance) at +77°F (+25°C), 50% RH
Reaction time: approx. 5 sec.
External sensor: cable 2 m with snap in connector (included)
Contact type: contact maker NO (MOSFET) or
contact breaker NC (MOSFET)
Service life: > 100,000 cycles
Operating voltage: DC 20 to 56 V
Optical indicator: LED
Connection: 6-pole terminal: stranded wire¹ AWG 16 (1.5mm²);
max. AWG 12 (2.5mm²)
Housing: plastic, UL 94V-0, grey (bicolor)
Mounting: clip for 35 mm DIN rail, EN 60715
Mounting position: vertical
Dimensions: 3.7 x 2.1 x 1.7” (93 x 53 x 44 mm)
Weight: approx. 4.2 oz. (120 g) incl. sensor
Operating/Storage temperature: -40 to +176 °F (-40 to +80 °C)
Operating/Storage humidity: max. 90% RH (non-condensing)
Protection type: IP20
Approvals: UL File No. E164102 / VDE / EAC
¹ When connecting with stranded wires, wire end ferrules must be used.

Variations

  1. DCT 011: 01011.0-31

    Max. switching capacity (relay output): DC 13 A
    Operating temperature: -22°F to +122°F
    Primary switching function – setting range temperature: 14 to 122°F
    Secondary switching function² – humidity setting: –
    Contact (primary): Contact maker (NO)

    ² Versions with secondary switching function can also register the humidity and therefore offer an additional protection for electronics.
    Switching difference: 4 % RH (±1 % tolerance) at +77 °F (+25 °C), 50 % RH.

  2. DCT 011: 01011.0-32

    Max. switching capacity (relay output): DC 11 A
    Operating temperature: -22°F to +140°F
    Primary switching function – setting range temperature: 32 to 140°F
    Secondary switching function² – humidity setting: –
    Contact (primary): Contact maker (NO)

    ² Versions with secondary switching function can also register the humidity and therefore offer an additional protection for electronics.
    Switching difference: 4 % RH (±1 % tolerance) at +77 °F (+25 °C), 50 % RH.

  3. DCT 011: 01011.0-61

    Max. switching capacity (relay output): DC 13 A
    Operating temperature: -22°F to +122°F
    Primary switching function – setting range temperature: 14 to 122°F
    Secondary switching function² – humidity setting: 65 % RH pre-set
    Contact (primary): Contact breaker (NC)

    ² Versions with secondary switching function can also register the humidity and therefore offer an additional protection for electronics.
    Switching difference: 4 % RH (±1 % tolerance) at +77 °F (+25 °C), 50 % RH.

  4. DCT 011: 01011.0-62

    Max. switching capacity (relay output): DC 11 A
    Operating temperature: -22°F to +140°F
    Primary switching function – setting range temperature: 32 to 140°F
    Secondary switching function² – humidity setting: 65 % RH pre-set
    Contact (primary): Contact breaker (NC)

    ² Versions with secondary switching function can also register the humidity and therefore offer an additional protection for electronics.