The electronic DC hygrostat with integrated switch module is used to control heating and cooling equipment, filter fans or signal devices through the relay.

  • High DC switching capacity
  • Adjustable humidity
  • Small hysteresis
  • Optical operating display (LED)
  • Integrated switch module
  • Precise measurement via an external sensor

Technical Data
Switching difference (humidity): 4% RH (±1 % tolerance) at +77°F (+25°C), 50% RH
Reaction time: approx. 5 sec.
External sensor: cable 2 m with snap in connector (included)
Contact type: contact maker NO (MOSFET) or
contact breaker NC (MOSFET)
Service life: >100,000 cycles
Operating voltage: DC 20 to 56 V
Optical indicator: LED
Connection: 6-pole terminal: stranded wire¹ AWG 16 (1.5mm²);
max. AWG 12 (2.5mm²)
Housing: plastic, UL 94V-0, grey (bicolor)
Mounting: clip for 35 mm DIN rail, EN 60715
Mounting position: vertical
Dimensions: 3.7 x 2.1 x 1.7” (93 x 53 x 44 mm)
Weight: approx. 4.2 oz. (120 g) incl. sensor
Operating/Storage temperature: -40 to +176 °F (-40 to +80 °C)
Operating/Storage humidity: max. 90% RH (non-condensing)
Protection type: IP20
Approvals: UL File No. E164102 / VDE / EAC
¹ When connecting with stranded wires, wire end ferrules must be used.

Variations

  1. DCF 010: 01012.0-20

    Max. switching capacity (relay output): DC 15 A
    Operating temperature: -22°F to +104°F
    Primary switching function – setting range humidity: 40 to 90% RH
    Secondary switching function² – Switch-on temperature: +41°F (+5°C) pre-set
    Contact (primary): Contact maker (NO)

  2. DCF 010: 01012.0-21

    Max. switching capacity (relay output): DC 13 A
    Operating temperature: -22°F to +122°F
    Primary switching function – setting range humidity: 40 to 90% RH
    Secondary switching function² – Switch-on temperature: +41°F (+5°C) pre-set
    Contact (primary): Contact maker (NO)

  3. DCF 010: 01012.0-22

    Max. switching capacity (relay output): DC 11 A
    Operating temperature: -22°F to +140°F
    Primary switching function – setting range humidity: 40 to 90% RH
    Secondary switching function² – Switch-on temperature: +41°F (+5°C) pre-set